AUTOCLAVE #3
OPERATIONS AND MAINTENANCE MANUAL
RELEASE 1.00
September
15, 2003
P.Koza
Please review for accuracy, organization and completeness.
Comments are greatly appreciated.
Autoclave #3 operations and maintenance manual
table of contents
.Begin Table C.
1.0 Introduction 1
1.1 HP-TDC-PLC
operation 1
1.2 Functional
Description Format 1
1.3 Reference
Designations 1
1.4 TDC and PLC
Tags 1
1.5 PID Loop Tags 2
1.6 Control Point
Tables Format 2
1.7 PID Control
Addressing 2
1.7.1 PID Loop Tags
vs. Loop number 2
1.7.2 TDC Interface
Tables 2
1.7.3 PLC PID
Parameter Tables 3
1.8 PLC & TDC
Data Tables 3
1.9 Contacts 4
2.0 Functional
Descriptions 6
2.1 Pressurization
System 6
2.1.1 Pressure
Control Points 6
2.1.2 Pressure System
Overview 6
2.1.2 Pressure System
Operation 6
2.1.3 Pressure
Startup 6
2.1.4 Pressure Holds
and Restarts 7
2.1.5 Auto Switch to
Air 7
2.1.6 Blowdown and
Blocking Valves 7
2.1.7 Pressure Gauges 7
2.1.8 Nitrogen Blocking
Valve 8
2.1.9 Pressure Valves
Adjustment 8
2.1.10 Pressure
Trouble 8
2.2 Purge Autoclave
Atmosphere 9
2.2.1 Purge Control
Points 9
2.2.2 Purge Operation 9
2.2.3 Purge, Add Air 9
2.2.5 Purge Caution 10
2.3 Man in
Autoclave 10
2.3.1 Man In
Autoclave Emergency Switch 10
2.3.2 MAN IN
AUTOCLAVE ALARM WILL DO THIS 10
2.3.3 Hyperbaric Unit 10
2.4 EMERGENCY STOP
PUSHBUTTON 10
2.4.1 ESTOP WILL DO 10
2.4.2 ESTOP
Differences 11
2.4.3 ESTOP Details 11
2.4.4 PLC NESTOP 11
2.4.5 ESTOP
Thermoflux 11
2.5 Temperature
Control 11
2.5.2 Block diagram 12
2.5.3 Part and Air
Temperature Control Loops 12
2.5.4 Outputs to
heating and cooling 12
2.5.6 Temperature
feedback, HP and/or PLC 12
2.5.7 Parts and
thermocouples 13
2.5.8 Setpoint Bias
and Feedback control 13
2.5.9 Modes of
Operation 13
2.5.10 Computer
Shed 14
2.5.11 Trouble 14
2.5.12 Heating
System by Thermoflux 15
2.5.13 Thermoflux
Documents 15
2.5.14 Thermoflux
SLC Program 15
2.5.15 Thermoflux
Start Up 15
2.5.16 Heating
System Alarms 16
2.5.17 Thermoflux
Published Limits 16
2.5.18 Specific
Heating Problems 16
2.6 Liquid Nitrogen
Cooling 17
2.6.1 Cooling Exhaust
Recirculation 17
2.6.2 LN2 Flow 18
2.6.3 LN2 Adaptive
Gain 18
2.6.4 LN2 adaptive gain calculations 18
2.6.5 Configured LN2
Points 19
2.7 MOTOR OPERATED
VALVES 19
2.7.1 Motor Operated
Valve Operation 19
2.7.2 MOV Timers and
Failures 19
2.7.3 Pressure System
MOVs 20
2.7.4 Blocking Valve
Vent MOV 20
2.7.5 Liquid Nitrogen
Source Select MOVs 20
2.7.6 Vacuum System
MOVs 20
2.7.7 Leak Test, Line
Test and Calibrate MOVs 20
2.7.8 PLC Program
Vacuum MOVs 20
2.7.9 Calibrate to
Air, or AWACS Back Pressure 21
2.8 Solvent
Extraction System 21
2.9 Oxygen Analyzer 22
2.9.1 Oxygen Analyzer
Maintenance and Calibration 22
2.9.2 Oxygen Analyzer
Operation 23
2.10 Set Point
Limiting for Air Temperature 23
2.10.1 Setpoint
Limiting Rational 23
2.10.2 Setpoint
Limiting operation 23
2.11 RTU FUNCTIONS 23
2.11.1 Resetting
the RTU System 23
2.11.2 RTU
System Description 25
2.11.3 RTU
Reference Manuals 25
2.11.4 ST3000
Smart Transmitters 25
2.11.5 RTU
System Details 26
2.11.6 MiniCOP 26
2.11.7 Subroutine
102 26
2.11.8 Read
MiniCOP to PLC 26
2.11.9 MiniCOP
Software Test 27
2.11.10 Stand
alone Minicop Program Test 28
2.11.11 Cold Boot
MiniCOP 28
2.11.12 DATACONTROL
Command Setup 28
2.11.13 GOTCHA 29
2.11.14 RTU Error
Detection 29
2.12 Blowers 30
2.13 Door Stuff 31
2.14 AWACS 32
2.14.1 Configured
points 32
2.15 STOP BEFORE
PRECURE 33
2.16 Initialize Run 33
2.17 Startup 34
2.17.1 Deviation
alarm limits 34
2.17.2 3QI126, OPERATOR
CONTROLD NOT BACKUP (1137) 34
2.17.3 3QI124,
OPERATOR CONTROLS READY (1150) 34
2.17.4 3QIRDY,
EQUIPMENT READY TO RUN (1125) 34
2.17.5 3QI155B,
CYCLE RUNNING 34
2.17.6 3QI152
CURE IS INITIALIZED 35
2.17.7 3QA110,
ALARM LIGHT 35
2.18 Fischer Valve manuals 36
3.0 PLC Program 37
3.1 Honeywell PLC 37
3.2 Referenced
documents 37
3.3 Using the PLC
Loader software 38
3.4 PLC Program
outline 40
4.0 TECHNICIAN
NOTES 52
4.1 mX + b Equation 52
4.1.1 Conversion 52
4.1.2 Thermocouple
scaling example 52
4.1.3 Pressurization
split range 53
4.2 Generic Control
Loop 53
4.3 PLC Programming
Notes 54
4.4 What would you
like here? 56
APPENDIX 56
1.0 Introduction
This document describes the functions and operation of the
autoclave hardware and Programmable logic controller (PLC) functions. The purpose and emphasis of this manual is
provide the level of detail necessary to operate and maintain the autoclave control
system. The level of discussion
presupposes that the reader is familiar with the purpose and normal operation
of the autoclave, that he/she is familiar with the Process and Control
diagrams, and has access to the vender manuals and design documents.
This manual describes the functions of the system from the
electro-mechanical process control devices, instrumentation, and
operation. The other two major
components, commonly known as the
"Computer", are the TDC 3000 terminals and communications network,
and the HP data collection computer.
The TDC provides the operator interface,
custom graphics and the trending and reports that are
available from the operator's consoles.
The HP computer provides the process recipes, supervisory functions, and
calculated part temperature. These
functions also include the cure definition, initialization, and the run data
report generation for QC.
1.1 HP-TDC-PLC
operation
Several functions require all three of the major physical components. An example of the three components working
together is the vacuum leak test. It is
usually started during initialization by the HP computer, which then transmits the
request across the TDC communications network to the PLC, which then performs
the valve changes for the test. The PLC
reads the vacuum transmitters and provides the data which can be read by either
the TDC or the HP Computer. The HP then
decides whether the test has passed or failed. This document concentrates on
the functions provided by the PLC.
1.2 Functional
Description Format
The functional descriptions include a description of the
high level function, operator controls and operation, and down to the details
of the actual valve and instrument operations (where it is necessary). There is a certain amount of overlap between
this section and the chapter with detailed program descriptions. Section ??.?, PLC Program, is used as an
adjunct to the documentation capabilities of the Honeywell Ms-Dos Loader
package. The line comments in the
program will often refer to the section in this document where additional
information can be found.
1.3 Reference
Designations
References to the physical components, such as valves and
gauges, are made with the standardized reference designations that are detailed
on page 1 of the Process and Control (P&Cs) diagrams. The three digit tag number is consistent
through the documentation package. This
number may be followed through the wiring diagrams to the PLC modules. One part of the wire number is the field
device and the other part is the terminal strip or module that it connects
to. The thermocouples and analog
outputs (from the PLC's viewpoint) connect directly to the modules. All other field devices connect to the back
panel terminal strips.
1.4 TDC and PLC
Tags
The hardware tag numbers are carried through the PLC to
the TDC with minor modifications. The
hardware pressure transmitters are "PT"s, while the TDC calls them
"PI"s. Thermocouples are
temperature elements in hardware and "TI"s on the consoles. The leading number on the TDC Tag is not
shown on the P&Cs since these drawings are specific to the Autoclave.
The switches in the TDC are called "Hand Indicating
Switch". The Tag name is built
from the prefatory autoclave number, "HIS", and the most relevant
item tag number. For example, the
Blowdown Switch, which locks the 4 inch vent valve open, is named
"3HIS302". The switches on
the TDC may be mapped to one or two points in the PLC. The TDC designation, "OP%" is the
output from the TDC to the PLC. In the
case of a switch it is a contact in the PLC program. The TDC designation "PV" is the input to the TDC from the
PLC. The PLC program will set the
on/off state of this element with a coil.
In the case where the PV and OP% have the same PLC address, it is
generally only a PLC contact. (Note
that this differs from the operator interface switches in the #6 Modicon. Refer to the PLC Programming notes in the
appendix for more details.)Tags, PLC vs. TDC
1.5 PID Loop Tags
An array of ten addresses per PID loop have been allocated
for interface to the TDC. Six of the
ten are configured as points on the highway.
The PV (PICxxx), OP (aka Process Demand), and SP are analog inputs. These are read only points that yield a
scaled indication on the TDC. The three
tuning constants are counters, which simply pass the non negative, 16 bit,
integer number. Since counters can not
pass a decimal point, the tuning constants values are entered times one
hundred, IE. a gain of 1 is entered as 100.
The PID loops are written by Bill Ware of Honeywell in ladder logic. They have additional tables of variables
used in the calculations. The most
significant items are the SP (written to) and the PV, which are in engineering
units times 10, such as PSI, Degrees F. and In Hg.
1.6 Control Point
Tables Format
The
start of each functional description includes a list of the major control
points that are related to the operation of the function, and are configured on
the highway. Each point includes the
TDC Tag name, which may be one or two PLC tags, the PLC address, and a
description of the function. The list
may have points in common with other functions. A detailed description of the points as they relate to the
function or internal programming is given in the text.
1.7 PID Control
Addressing
1.7.1 PID Loop Tags
vs. Loop number
The PID routine is written in ladder logic. It uses several tables of values that are
accessed by indirect address operations.
The actual datum address is determined by the beginning address of the particular
table plus the loop number. The
correlation is:
LOOP # LOOP TAG FUNCTION
1 3PIC300 Autoclave Pressure
2 3TIC500 Part temperature
3 3TIC540 Air temperature
4 3FIC600 Circulation Blower Horsepower
control
5 3PIC450 Header 1 (West) vacuum
6 3PIC460 Header 2 (East) vacuum
7 3PIC440 (AWACS) Back pressure
1.7.2 TDC Interface
Tables
The formatted data items on the TDC screens are usually
done with the point type Analog Input, (AI).
This allows the display to have a decimal point and/or a negative
sign. Since the PLC uses integer
arithmetic (without a decimal point) and the TDC Highway can not pass a
negative number, this point type allows the transfer of real numbers. This point type expects the register value
to be in the range of 0 to 4095 counts.
The configured TDC low and high end engineering units are obtained from
the point detail display, second page.
The TDC configured parameters for each loop are in a group of 10
successive registers. The effective
address is calculated as 10 times the loop number plus the starting
address. The table below gives this
correllation. The Point Type
"XX" means that this point is not configured on the Highway.
HIGHWAY
INTERFACE TAGS
Parameter Point
Type Start Addr.
PV in Engn. Units (read only) XX 6141
Process demand (Output) AO 6142
SP in Engn. Units (PLC writes) XX 6143
K Proportional gain .01 - 99.9 C 6144
T1 Integral gain Min/Repeat C 6145
T2 Deriv. gain (rate) Minutes C 6146
Low end PLC engn units XX 6147
High end PLC engn units XX 6148
A/D input bias (4 mA offset) XX 6149
SP in 0-4K counts read only AI 6150
T3 Tuning, rate decay time C 6620
The low and high end Engineering Units values in this
table is used only within the PLC. The
TDC and the HP maintain their own copies of these values. Also, the smart transmitters are generally
set up with these same scaling values.
1.7.3 PLC PID
Parameter Tables
The TDC interface tables are written to and from another
set of tables. These are not configured
on the TDC Highway. They are accessed with
indirect address registers. The
effective address is calculated as Loop Number plus Starting Table
Address. These items and two coils are
given below.
PID
TABLES
Parameter Starting
Address
Output (Process Demand) 5970
A/D raw analog input 5520
PV in engn units (X 10) 6020
MCC Manual Control Command (PD in Man.) 5190
Scan flag 1900
Auto (On) / Manual Mode flag 1650
Proportional term (K X error) 5920
Integral term 5720
Derivitive term (Rate action) 5570
The last three values are useful for watching the effects
of the tuning constants. Refer to
volume 1 of the Honeywell 626-1202 Manual for an explanation of how all of this
works.
1.8 PLC & TDC
Data Tables
The three methods of getting analog information into the
PLC (and to HP and TDC) from real I/O are Thermocouple Modules, Analog Input
Modules, and the Novatech RTU. The
highway can not access any of these devices directly, so the PLC
"Pulls" the data, massages the values, and puts them into
tables. The starting address of these
tables are given as a guide to where they are located in the tag listings. These addresses can be "Searched"
for in the PLC program to find rungs that show the table.
Start of Operator switches and indicators 1000
Open current loop status 1101
PID Deviation alarms 1200
Vacuum valves, source select 1401
Solvent extraction valves select 1451
Deviation alarms limits (Engn. X 10) 4111
Cure specification (downloaded) 4201
Cure specs, same table, used by PLC in run 4701
Analog Inputs, (rescaled 0 to 4095) 4330
RTU data table (0 to 4095) 4350
Thermocouple inputs 4400
Thermoucouple channel open status 4501
RTU channel status (register values) 7950
RTU channel status (coils) 1550
Search for 1566 and 1582
RTU channel ignore bad channel registes 5101
1.9 Contacts
These venders and representatives
have been involved in the Autoclave Modernization Project. They can provide technical and/or repair
information.
Honeywell:
Mike Keser, PLC expert, sales representative, and a helpful soul.
He does not handle this area any more, but can frequently answer technical
questions off the top of his head.
(503) 526-5113.
Repairs of PLC hardware, L.A. (800) 423-3704 Give them a P.O. number for repairs and priority orders for
replacement.
Repairs and parts for Smart Transmitters and other
Honeywell products: (800) 223-8947.
Mark Michaels, TDC equipment sales representative
and service. Bellevue: 453-7559. His voice message box is 559. (He has the telephone number for Service
Dispatch) Steve Buck is the TDC
Technical service representative for this area.
Honeywell ICD, PLC headquarters in York Pa. (717) 848-1151 The next four people can be reached with this number. The accuracy of the information from some of
the people at this office leaves room for improvement.
Bill Ware, PID routines author and most
knowledgeable person in the PLC (IPC) division at York, Penn.
Scott Young, MiniCop Basic Program author and
general PLC information. Contact at
York, Penn. Ask for Marketing.
Tom Deller, Technical Services, York, Penn. PLC classes and documentation.
Les Furguson, Mgr. of MS-DOS Loader/Terminal
software. Feel free to call him at any
hour of the day or night if you encounter problems with the Loader software.
TDC Technical Support, Consultation fees paid
through July 1989. Daytime, Az. hours. (800) TAC-PMSD Tell them the System Number is "HWJ".
Bud Gaynot (215)641-3402, Dick Lucas (X3405)
Engineers for smart transmitters at Ft. Worth, Penn. They are very interested the quality of the smart
transmitters. They will want a Detailed
description of problems and/or failures of any Smart Transmitters.
Worcester "Wooster" and SVF Motor
Operated Valves:
Industrial Valve and Fitting Co.
922-3175
AUSCO Valves:
Automatic Switch Co, Bellevue 454-6167
Larry Blane, George Ross, Jack Mosteller
Fischer Valves and Flow Sensors:
PCE Pacific Co. of Bellevue, 823-2112
Tom Fritsler is very knowledgeable about all of the green valves. Get the Serial Number off of the valve,
along with the other ratings on the plate before calling him. (They keep records of all valves by serial
number.)
ISI, Woodinville, HP software:
481-6325 Contacts: Ken Roberts, Michael
Robbins. Normally coordinate these
calls through Rob Stitt in Facilities Engineering, X1-3427
Novatech, RTU manufacturer. Information contact: Arlen Nipper , Bob Sardou (913)
491-3248 Office hours in Kansas City, 8
am. to 5 pm.
Honeywell sold their equipment as an "Off the Shelf" item, but has
not done very well with support and/or information. Novatech is a small company which will be much more helpfull than
York, Pa.
Thermoflux, heating system manufacturer on AC #3
and AC #5. Bob Moon,(918) 747-9394
2.0 Functional
Descriptions;
.2.1 Pressurization
System
2.1.1 Pressure
Control PointsPressure Control
Points
3HIS300 Backup
pressure control
3PC300S Setpoint for backup pressure
3HIS302 Open and lock blowdown valve
3HIS320 Close and lock N2 gas blocking
valve
3HIS310 Air/Gas select
3PIC300 Pressure PV in use by PID
controller
3PC300SP Read only Set Point
3PC300OP Read only Process demand
3PI301 Pressure gauge #1
3PI302 Pressure gauge #2
3HIS301 Select pressure gauge #2
3QAD301 Pressure gauges differ by >
2%
2.1.2 Pressure System
Overview
The autoclave may be pressurized with either plant air or
with nitrogen. The plant air pressure
is regulated down to about 100 to 110 PSI.
The nitrogen source is directly off the accumulators, so that this
pressure can vary from a low of 160 PSI to a high of 365 PSI. The control valves for filling the autoclave
are located at the south east corner of the chamber. The 1 inch and the 4 inch vent control valves are located on
top. The autoclave has two safety relief
valves that will open at about 225, depending on temperature, and a rupture disk
that is currently 225 PSI at 350 degrees.
A high pressure limit switch is located by the door controls. It will shut down the fill valves and open
the vents until the pressure returns below the limit, which is a drop of about
25 PSI. Under fault conditions of a
stuck open fill valve, it will cycle on and off; this will be a noticeably
dramatic event.
2.1.2 Pressure System
Operation
The pressure system is automatically controlled during a
normal run by the cure specifications.
Operator intervention is only necessary to handle exceptional
circumstances, but even Backup will not allow pressure in the autoclave if the
equipment and controls are not ready.
Equipment Ready and Operator Controls Ready are necessary to start a
run.
means that the door is
closed and locked, there is no Man-In-Autoclave alarm, nor is the Emergency
Stop button pushed in. The Ping Pong
Valve closed status is part of the Operator Controls Ready indicator. The manual section entitled
"Startup" lists the complete definition of these indicators.
Initialization on the HP Computer will set the autoclave
to use nitrogen. Closing the door will
turn on the automatic purge switch. The
start-up screen also contains the Auto Switch To Air on Cooldown switch. It should be left on. Ocassionally, these controls will end up set
incorrectly. The Equipment Status
screen will tell you what is preventing startup.
2.1.3 Pressure
Startup
The normal cycle starts with pressurization to the Vent
Bags Pressure. The pressure ramp is put
on hold until the bags are actually vented.
If the bags do not vent for some reason, then pressure will not
continue. This hold can not be turned
off by the operator. The Post
Pressurization Leak Test, abbreviated PPLT, is ocassionally used
after pressure is applied, but before the bags vent. The system turns on Operator Hold when this specified pressure
(setpoint) is reached. The operator is
expected to initiate the test and to turn off the hold after it is complete.
2.1.4 Pressure Holds
and Restarts
The hold on the temperature system is generally released
when the pressure is at the first (and usually only) soak pressure. If the pressure does not come up to this
setpoint, then the temperature hold may not be released. The temperature hold release may be
specified in the cure to release at a number of minutes into any pressure
segment. If the temperature hold does
not release as expected, check the cure specification pages. Pressure may be held by temperature and
released when either the Part Temperature reaches the specification, or at a
number of minutes into a temperature segment.
Since pressure can hold and release temperature, and temperature can
hold and release pressure, it is possible to devise a cure specification that
will lock up. No parts use this lockup
cure at present, but the option exists if it becomes necessary.
Most cures call for continuous pressure over the entire
cycle, but more than one pressure ramp and soak level may be specified. The run moniter shows the presure segment
number and the soak time remaining.
These segments and times are what is specified on the Cure screens. Odd segments are ramps
and Even segments are soaks.
2.1.5 Auto Switch to
Air
The Auto Switch To Air on Cooldown function uses the cure specification to select Air
during the last cooldown ramp. The
pressure in the autoclave must be below 100 PSI, and the Part Temperature must
be below 280 degrees. The switch to air
is accompanied by the sound of the nitrogen blocking valve closing. This event also initiates the Purge
function. Refer to the Purge discussion
below.
2.1.6 Blowdown and
Blocking Valves
The Blowdown can occur for several
reasons. The normal blowdown occurs
when the last temperature soak at room temperature is completed. The pressure soak timer may also time out,
although this is rarely used. The
Emergency Stop Button will blowdown, but Man-In-Autoclave will not. Unintentional intervention may also cause
blowdown and/or termination of the cure cycle.
That is the right autoclave that you have up on the screen, isn't
it? Turning off the power to the PLC
will cause termination of the run, as will putting it into Program Mode.
The Blowdown Switch and the Nitrogen
Blocking Valve Switch on the Startup Screen
are there for emergency use. Normally,
they need not be touched. The Blowdown
switch will over ride the automatic functions and open the vents and close the
fill valves. The Nitrogen Blocking
valve will close this valve and keep it closed. Before starting a run, the Blowdown Switch indicater will say
"BLOW", and the output will say "CLOSE". The indicator will change to
"CLOSE" once the run is started.
The blocking valve output will indicate "OPEN" and the
indicator will say "CLOSED" before the run. At the start of the run, the indicator will change to
"OPEN" if nitrogen has been selected. Stated simply, you can force the blowdown valve open but you can
not force it closed. You can force the
Nitrogen Blocking Valve closed, but you can not force it open.
Pressure Backup will not allow pressure if the equipment
and controls are not correct. It is
used primarily for testing, but it is necessary to put pressure and temperature
into backup if the run gets trashed by a power bump, ESTOP, or other
operational anomolies.
2.1.7 Pressure Gauges
Two Pressure gauges are provided for controlling autoclave
pressure. The alarm 3QAD301 indicates that these two
transmitters read differently by more than 2%. If you get this alarm, look at the two
readings on the Bypass screen. A failure of the gauge being used to control
pressure will cause one of two events: either full pressurization or complete
venting. The switch that selects which
gauge to use is also on this screen, it is 3HIS301. These gauges are operated in analog mode and do not go through
the RTU. This means that the readings
will go seriously amuck if someone connects the Smart Field Communicator, (SFC)
to the gauge. If this occurs during a
run, switch to the other gauge and go discuss family lineage with them.
2.1.8 Nitrogen
Blocking Valve